Trio2Sys - Modular 4-channel LED EnOcean counting receiver
10020110
In stock. Ordered before 5pm, delivered the next business day.
CHF115.00
Tax included
In stock 2 Items
The 4-channel modular receiver receives and processes radio signals from transmitters or sensors within its range to switch LED and compact fluorescent lighting loads.
Modular 4-channel LED receiver with EnOcean metering
The modular 4-channel switch receiver is used to receive radio signals from EnOcean switch transmitters or sensors.
Designed for switching LED and compact fluorescent lighting loads, it can also switch resistive loads (halogen), fluorescent tubes, low-voltage halogen lamps with ferromagnetic and electronic transformers, power contactors or small motors.
The 4-channel switch receiver is equipped with a repeater function and a consumption indicator function.
FUNCTIONS :
- 4-channel 1.5A receiver module
- 4 control channels in 1 module
- EnOcean technology
- Remote control of lights/appliances
- ON/OFF function
- Supports any type of load
- Up to 32 transmitters can be assigned (switches, presence detectors, or magnetic window or door contacts)
- Zero Crossing technology
- Power consumption metering
- Repeater and status feedback functions
- DIN rail mounting
- Easy to install and use
TECHNICAL SPECIFICATIONS :
- Power supply : 230V~ / 50 Hz
- Power consumption : <0,35W (relays disabled)
- Output load:
- Resistive load : 4 x 1,5A max (Cos φ=1)
- LED: 4 x 130W
- Inductive: 4x 300W with cosφ=0.4 to 0.6
- Halogen: 4 x 345W
- Fluorescent: 4 x 130W
- Measurement accuracy (power): 2% ± 1 digit (for power <10W)
- EnOcean Equipment Profile: D2-01-00 (power consumption) / A5-3F-00 (radio test)
- Number of associable transmitters: Up to 32 transmitters and magnetic window contacts
- Dimensions: 17.5 mm x 97.4 mm x 66.4 mm (1 DIN rail slot)
- Operating temperature : -10 to +45°C
- Humidity: 0% to 75% relative humidity (non-condensing)
- Transmission frequency: 868.3MHz
- Range in buildings:
- Masonry: 20m, through up to 3 walls
- Reinforced concrete: 10m, through 1 wall/ceiling maximum
- Plasterboard / Wood: 30m, through up to 5 walls
- Use
- Energy Use Monitoring
Fixture Control
Lighting Control
Signal Enhancement - Type
- Module Rail Din
- Function
- Actuator
Electricity Consumption - Protocol
- EnOcean